| Model | Mercury 2000-S0 / 3000-S0 / 3600-S0 |
| Max. efficiency | 97.5% / 97.8% / 97.8% |
| European weighted efficiency | 96.5% / 96.8% / 96.8% |
| Max. input voltage | 500 V |
| Max. panel config (STC) | 1.5 |
| Rated input voltage | 360 V |
| Max. input current | 13 A |
| Max. short-circuit current | 15 A |
| Start-up input voltage | 70 V |
| MPPT operating voltage range | 50 V - 490 V |
| Number of MPPT strings | 1 |
| Number of MPPTs | 1 |
| Rated AC active power | 2,000 W / 3,000 W / 3,600 W |
| Max. AC apparent power | 2,200 VA / 3,300 VA / 3,600 VA |
| Max. AC active power (PF=1) | 2,200 W / 3,300 W / 3,600 W |
| Max. AC output current | 10 A / 15 A / 16 A |
| Rated AC voltage | 220 V / 230 V, L+N+PE |
| AC voltage range | 160 V - 300 V (adjustable) |
| Rated grid frequency | 50 Hz / 60 Hz |
| Grid frequency range | 45 Hz - 55 Hz / 55 Hz - 65 Hz (adjustable) |
| Total harmonic distortion (THDi) | <3% (at rated power) |
| DC injection | <0.5% In |
| Power factor | >0.99 at rated power (adjustable 0.8 lead - 0.8 lag) |
| DC switch | Supported |
| Anti-islanding protection | Supported |
| AC overcurrent protection | Supported |
| AC short circuit protection | Supported |
| DC reverse polarity protection | Supported |
| Surge arrester | DC Class III (optional) / AC Class III |
| Insulation impedance detection | Supported |
| Leakage current protection | Supported |
| Topology | Transformerless |
| Protection degree | IP65 |
| Night self-consumption | <1 W |
| Cooling | Natural |
| Operating temperature range | -25℃ - 60℃ |
| Allowed relative humidity range | 0 - 100% |
| Max. operating altitude | 4000 m |
| Typical noise level | 30 dB |
| Dimensions (W*H*D) | 320 mm * 344 mm * 137 mm |
| Weight | 6.5 Kg |
| Display method | Wireless & APP + LED, LCD (optional) |
| Communication interfaces | WiFi (optional) / GPRS (optional) / RS485 (optional) |
| Safety certification | IEC62109-1, IEC62109-2 |
| Grid code standards | IEC61727 / 62116, ABNT 16149 / 16150, IEEE 1547, AS 4777 |
| Warranty | 5 years |